Bottom Outlet Heaters

Models
Options
Cad Drawings
Manuals
Application Data


                             


Bottom Outlet  Heaters

Installation, Operation, and Maintenance Instructions

1.0 Handling

	1.1 	Unpack and handle with care to avoid damage to heater and
		components

	1.2 	Make sure heater is protected from contamination during
	      	storage. A dry environment if preferred.

	1.3	Refer to Application Data link for additional information
		related to heater system design and selection.


2.0 Safety

	2.1 	WARNING: Make sure power supply is turned off before 
	      	installation or service of electric heater to prevent electrical
	      	shock or damage to equipment.

	2.2 	WARNING: Circuit should have separate disconnect means 
		which shall be capable of being locked in the open position
	      	and also in sight from the heater.

	2.3 	WARNING: Wiring must conform to the National Electric
 	      	Code and Local Regulations and should be performed by a
 	      	a qualified electrician. Make sure wiring is of a suitable 
	      	temperature rating, amperage rating, and the location.

	2.4 	WARNING: When servicing, handle with caution, the heater
	      	surface may be hot.

	2.5 	WARNING: Do not install heater into a medium or an
	      	environment that could result in an explosion, fire, or
	      	hazardous condition. Contact Vulcan regarding heaters that
	      	are specifically designed for hazardous locations.

3.0 Installation and Operation

	3.1 	Caution: Make sure the heater supply voltage is the same
		as the rated heater voltage.

	3.2 	Caution: Heater should be properly grounded to prevent
	      	electrical shock hazard

	3.3 	Caution: Do not support or suspend heater from termination
	      	or wiring

	3.4 	A common cause of heater failure is contamination of the 
 	      	the internal heater components through the termination end 
	      	of the heater. Make sure the heater is protected from 
	      	contamination in the final application. 

	3.5   	Make sure heater termination is not exposed to water or
	        	other liquids. Make sure that no dripping from
		condensation on cold water pipes or other sources can fall 
		on any exposed electrical wiring connections or components.

	3.6.  	Termination's should be properly tightened and connected
	        	to hook-up wiring. A loose connection will result in over-
	        	heating at the connection and could lead to premature 
	        	failure. Where possible, use a wrench or pliers to prevent
	        	twisting of the terminals during installation.

	3.7   	Bottom Outlet heaters are designed for installation through
		a 2-7/16" diameter hole in the bottom of a tank or vessel. 
		Heater tubes must be covered by water at all times during 
		operation. Care should be taken to avoid air entrapment
		or pockets of overheated fluid around the heater tubes.

	3.8	Center compression bolt with gasket must be properly 
		tightened to ensure a leak tight joint. Check joints for leaks.

	3.9 	Models with cut-out switch are designed to shut down the 
		heater in event of a drop in water level. Other basic models 
		do not include a switch. System should include a safety device
		such as an over temperature thermostat or low liquid level 
		cut-out switch. Heater tubes are designed for direct immersion
		and will fail if operated in air and may cause other damage.

	3.10	Heater should be wired performed per diagram supplied with
		unit or refer to our following website page for common circuits:
		Common Wiring.pdf

	3.11	Do not exceed 105% of rated voltage. Higher voltages result in 
		higher wattage output which could damage the heater, system, 
		or medium heated.

	3.12 	Models equipped with a low water cut-out thermostat-

		3.12.1 	Do not exceed amperage rating of thermostat. The
			cut-out thermostat included as an option on some
 			models is rated at 30 amps at 300 volts max.

		3.12.2 	The thermostat is a manual reset type (requires
	  		operator to push button in event of an trip condition)
	
		3.12.3 	Thermostats are designed for heater control only and
           			are not intended for use as a direct control of motors, 
  			pumps, or other devices.

		3.12.4 	Do not use thermostat as a power disconnection
  			means for the heater assembly.


4.0 Maintenance

	4.1	For most applications, no heater maintenance is required.

	4.2   	Disconnect line switch prior to any testing or work on the heater

	4.3  	Check heater termination's after the initial 8 hours and tighten any 
		loose terminal and jumper connections. 

	4.4 	Recheck wiring periodically to ensure wiring has not become 
		damaged, worn, or loose due to vibration or other application 
		related conditions. Tighten, repair, or replace as needed.

	4.5	Heater tubes should be checked periodically for scaling or mineral 
		deposits on heater tubes and cleaned as required.


5.0 Trouble Shooting

	5.1	WARNING: Disconnect power supply to heater(s) before performing
		any trouble shooting procedures.
 
	5.2   	Check supply voltage to heater to ensure there is power.
 
	5.3  	Check wiring circuit- make sure heater is properly wired and all 
		supporting controls, relays, contactors, and other circuit related
		switches are also properly wired and functional. 

	5.4 	Check heater(s)- No heat due to a heater failure is generally due
		to an open heater circuit. Check heater resistance across both
		terminals or leads. A reading of infinity (no continuity) indicates an
		open circuit within the element and the heater must be replaced. 

	5.5  	Longer than normal heat up time for units with more than one 
		heating element may be the result of an individual heating element
		failure.

 


Copyright © 2004 Vulcanelectric.com. All rights reserved.