Over-The-Side Heaters

Models
Options
Cad Drawings
Manuals
Application Data


                             
 
 
Over-The-Side Heaters

Installation, Operation, and Maintenance Instructions
 
1.0 Handling

	1.1 	Unpack and handle with care to avoid damage to heater and
		components

	1.2 	Make sure heater is protected from contamination during
	      	storage. A dry environment if preferred.

	1.3	Refer to Application Data link for additional information
		related to heater system design and selection.


2.0 Safety

	2.1 	WARNING: Make sure power supply is turned off before 
	      	installation or service of electric heater to prevent electrical
	      	shock or damage to equipment.

	2.2 	WARNING: Circuit should have separate disconnect means 
		which shall be capable of being locked in the open position
	      	and also in sight from the heater.

	2.3 	WARNING: Wiring must conform to the National Electric
 	      	Code and Local Regulations and should be performed by a
 	      	a qualified electrician. Make sure wiring is of a suitable 
	      	temperature rating, amperage rating, and the location.

	2.4 	WARNING: When servicing, handle with caution, the heater
	      	surface may be hot.

	2.5 	WARNING: Do not install heater into a medium or an
	      	environment that could result in an explosion, fire, or
	      	hazardous condition. Contact Vulcan regarding heaters that
	      	are specifically designed for hazardous locations.

3.0 Installation and Operation

	3.1 	Caution: Make sure the heater supply voltage is the same
		as the rated heater voltage.

	3.2 	Caution: Heater should be properly grounded to prevent
	      	electrical shock hazard

	3.3 	Caution: Do not support or suspend heater from termination
	      	or wiring

	3.4 	A common cause of heater failure is contamination of the 
 	      	the internal heater components through the termination end 
	      	of the heater. Make sure the heater is protected from 
	      	contamination in the final application. 

	3.5   	Make sure heater termination is not exposed to water or
	        	other liquids. Make sure that no dripping from
		condensation on cold water pipes or other sources can fall on
		any exposed electrical wiring connections or components.

	3.6.  	Terminations should be properly tightened and connected
	        	to hook-up wiring. A loose connection will result in over-
	        	heating at the connection and could lead to premature 
	        	failure. Where possible, use a wrench or pliers to prevent
	        	twisting of the terminals during installation.

	3.7   	It is good practice to avoid routing of thermocouples with 
	        	power wiring. Use separate conduit. Thermocouples, 
	        	thermostat capillary tubes, and wiring should be kept clear
	        	of heater terminals by distance or appropriate insulation.

	3.8	Over The Side heaters are designed for direct immersion into 
		a liquid. Heater tubes must be installed into the system so
		that the tubes are covered by liquid at all times during
		operation. Care should be taken to avoid air entrapment 
		or pockets of overheated fluid around the heater tubes.

	3.9	Heaters are designed for placement into tanks with the
		heating element portion of the assembly immersed at the 
		bottom of the tank and the terminal enclosure above the tank. 
		The heating element tubes (either straight or circular shaped 
		depending on model) provide the heat.

	3.10	Support legs are provided on the heating elements to elevate 
		the heater off the surface and away from the sludge. Make 
		sure sludge does not build up around the heater tubes.

	3.11 	Heater tubes are designed for direct immersion and will fail
		if operated in air.

	3.12	Heater wiring should be performed per diagram supplied with
		unit or refer to our following website page for common circuits:
		Common_Wiring.pdf

	3.13  	Do not exceed 105% of rated voltage. Higher voltages result 
		in higher wattage output which could damage the heater,
		system, or medium heated.

	3.14 	Units equipped with a thermostat-

		3.14.1 	Do not exceed amperage rating of thermostat.
	
		3.14.2 	Thermostats are designed for heater control only and
           			are not intended for use as a direct control of motors, 
  			pumps, or other devices.

		3.14.3 	Do not use thermostat as a power disconnection
  			means for the heater assembly.

	3.15	Check for proper installation of conduits and covers to 
		ensure terminal box protection. Make sure gaskets seat 
		properly on units equipped with moisture resistant 
		terminal boxes.


4.0 Maintenance

	4.1	For most applications, no heater maintenance is required.

	4.2   	Disconnect line switch prior to any testing or work on the
		heater

	4.3  	Check heater terminations after the initial 8 hours and tighten 
		any loose terminal and jumper connections. 

	4.4 	Recheck wiring periodically to ensure wiring has not become 
		damaged, worn, or loose due to vibration or other application 
		related conditions. Tighten, repair, or replace as needed.

	4.5	Heater tubes should be checked periodically for scaling or 
		mineral deposits on heater tubes and cleaned as required.


5.0 Trouble Shooting

	5.1	WARNING: Disconnect power supply to heater(s) before 
		performing any trouble shooting procedures.
 
	5.2   	Check supply voltage to heater to ensure there is power.
 
	5.3  	Check wiring circuit- make sure heater is properly wired 
		and all supporting controls, relays, contactors, and other
		circuit related switches are also properly wired and functional. 

	5.4 	Check heater(s)- No heat due to a heater failure is generally 
		due to an open heater circuit. Check heater resistance across
		both terminals or leads. A reading of infinity (no continuity) 
		indicates an open circuit within the element and the heater 
		must be replaced. 

	5.5  	Longer than normal heat up time for units with more than one 
		heating element may be the result of an individual heating 
		element failure.

 


Copyright © 2004 Vulcanelectric.com. All rights reserved.